Ionisation Flame Monitor D-IO 55
Ionisation flame monitor for intermittent or continuous operation. Also suitable for single electrode operation in conjunction with DURAG ignition transformers, model D-HG 55 |
 |
|
Features |
| |
|
 |
monitoring of gas and oil burners of any load |
 |
suitable for intermittent operation and continuous operation |
 |
simple installation on TS 35 DIN-rail |
| |
|
|
Applications |
| |
|
 |
Chemical industry |
 |
Refineries |
 |
Cement plants |
 |
Waste incinerators |
 |
Heating plants |
 |
Steam generators |
| |
|
|
Flame monitor (control unit)
|
| Operational mode
| intermittent or continuous operation
|
| Supply voltage
| 115 / 230 VAC, 50 / 60 Hz
|
| Perm. ambient temperature
| -20...+60°C
|
| Safety time
| 1 s, 3 s or 5s
|
| Display
| LED
|
| Protection
| IP20
|
| Flame relay
| 1 relay output 250 VDC / 2 A
|
| Installation
| DIN-rail TS 35
|
| Dimensions
| 70 x 75 x 118 mm (LxWxH)
|
| Weight
|
approx. 0.3 kg
|
|
Flame sensor
|
| Spectral sensitivity
|
D-LE 55 ISF-CG: 790 – 1050 nm D-LE 55 UL-CG: 190 – 270 nm
|
| Perm. ambient temperature
| -20...+60°C
|
| Installation
| G 1“ or G ½“
|
| Protection
| IP 67
|
| Dimensions
| Ø27 mm, length 116 mm
|
| Weight
| 0.45 kg |