Home    English    Deutsch    Français    Partners    Sitemap    Impressum  

 

 
Ionisation Flame Monitor D-IO 55
 

Ionisation flame monitor for intermittent or continuous operation.
Also suitable for single electrode operation in conjunction with DURAG ignition transformers, model D-HG 55
 

Features

   

monitoring of gas and oil burners of any load

suitable for intermittent operation and continuous operation
simple installation on TS 35 DIN-rail
   

Applications

   

Chemical industry

Refineries

Cement plants

Waste incinerators

Heating plants

Steam generators
   

Flame monitor (control unit)

Operational mode intermittent or continuous operation
Supply voltage 115 / 230 VAC, 50 / 60 Hz
Perm. ambient temperature -20...+60°C
Safety time 1 s, 3 s or 5s
Display LED
Protection IP20
Flame relay 1 relay output 250 VDC / 2 A
Installation DIN-rail TS 35
Dimensions 70 x 75 x 118 mm (LxWxH)
Weight

approx. 0.3 kg

Flame sensor

Spectral sensitivity

D-LE 55 ISF-CG: 790 – 1050 nm
D-LE 55 UL-CG: 190 – 270 nm

Perm. ambient temperature -20...+60°C
Installation G 1“ or G ½“
Protection IP 67
Dimensions Ø27 mm, length 116 mm
Weight 0.45 kg

More information 


 