Gas Fired Igniters

Heat Release max. 2000 kWtl_files/dg/images/logos/hegwein_150.gif

  • Applications
  • Technical Data
  • Downloads
  • Igniter and pilot burner for lean gas burners, heavy fuel oil burners or warm-up burners
Common Data  
Outer tube diameter 160 mm
Flame length max. 3000 mm
Outer tube length
(in 10 mm increments from - to)
300 - 4000 mm
Gas port Rp 2, top or bottom
Gas inlet pressure 50 - 150 mbarg
Air port DN 100 PN 6, rotatable 4 x 90°
Air operating pressure 10 mbarg, plus another 10 mbarg for every m of outer tube length
Power head (not ZG4)  
Ignition 2 x 5 kV, ignition electrode against ignition electrode
Ambient temperature - 30 °C to + 60 °C
Protection rating IP 54 or IP 65
Models  
without electrical components ZG4...
with integrated spark transformer ZT4...
with integrated spark transformer and ionisation flame monitor for intermittent operation ZA4...
with integrated spark transformer and ionisation flame monitor for continuous operation ZDA4...
with integrated spark transformer and burner control for intermittent operation ZR4...
with integrated spark transformer and burner control for continuous operation ZD4...