| Common Data | |
| Outer tube diameter Outer tube length up to 4000 mm Outer tube length from 4000 mm |
65 mm 70 mm For the stainless steel version always dia. 70 mm |
| Flame length (depending on the gas) |
max. 1200 mm |
| Outer tube length (in 10 mm increments from - to) |
240 - 15000 mm |
| Gas port | Rp 3/4, top or bottom |
| Gas inlet pressure | 50 - 150 mbarg |
| Air port | Rp 1½, rotatable 4 x 90° |
| Air operating pressure | 20 mbarg, plus another 13 mbarg for every m of outer tube length |
| Power head (not ZG1) | |
| Ignition | 5 kV |
| Ambient temperature | - 30 °C to + 60 °C |
| Protection rating | IP 54 or IP 65 |
| Models | |
| without electrical components | ZG1... |
| with integrated spark transformer | ZT1... |
| with integrated spark transformer and ionisation flame monitor for intermittent operation | ZA1... |
| with integrated spark transformer and ionisation flame monitor for continuous operation | ZDA1... |
| with integrated spark transformer and burner control for intermittent operation | ZR1... |
| with integrated spark transformer and burner control for continuous operation | ZD1... |