Ignition and burner control for
| type | BWO(EE) 2/2 SV98H-CR | BWO(BG) 2/2 SV98H-CR |
| function | ignition, flame detection and remote start | ignition, flame detection and remote start |
| design | EEx d enclosure for ignition unit and relays | Ex d enclosure for ignition unit and relays |
| EEx e enclosure for terminals | Ex e enclosure for terminals | |
| spark energy | appr. 8 J | appr. 8 J |
| spark tension | 2000 Volt | 2000 Volt |
| spark frequency | 2 Hz | 2 Hz |
| power supply | 115 or 230 Vac | 115 or 230 Vac |
| power consumption | 25 VA | 25 VA |
| enclosure | painted steel | aluminium painted (Ex d) 316 SST, painted (Ex e) |
| dimensions | 605 x 235 x 268 mm | 576 x 276 x 217 mm |
| protection | IP 65 | IP 66 |
| temperature range | -20 to 60 °C | -20 to 55 °C |
| remote start relay | 24 VDC | 24 VDC |
| flame relay | ionisation SV98H | ionisation SV98H |
| explosion proof | ATEX II 2G EEx de IIC T6 | ATEX II 2G Ex de IIC T6 |
| option | GOST-R certificate -40 to 60 °C |